Home / MS parts / NSN 5925-00-896-9626
NSN 5925-00-896-9626  ·  NIIN 008969626  ·  FSC 5925
NO DASHES 5925008969626
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

36 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 3.063
AFJNFRAGILITY FACTORMODERATELY RUGGED
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 250.0
AJECBOSS HEIGHTINCHES NOMINAL 0.156
TESTTEST DATA DOCUMENTDRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING) 06845-2055458
AKPXPOLE QUANTITY1
MATTMATERIALCASE PLASTIC
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 0.300 AND MAXIMUM AT 200 PCT 0.900
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
CPRQRESET METHODMANUAL
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDEXPLOSION RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 9.750
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 3.239
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 2
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 3.719
ADATBODY WIDTHINCHES NOMINAL 0.990
FREQFREQUENCY IN HERTZ60.0
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 50.0
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.750
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 1500.0
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC-HYDRAULIC