Home / MS parts / NSN 5925-00-810-9360
NSN 5925-00-810-9360  ·  NIIN 008109360  ·  FSC 5925
NO DASHES 5925008109360
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

42 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 2.500
ADATBODY WIDTHINCHES NOMINAL 2.250
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.750
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.062
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 0.750
CQSMSWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 4.000 AND MAXIMUM AT 200 PCT 10.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
CRTKSWITCH TERMINAL TYPETAB, SOLDER LUG
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 5.0 AND DC 1.0
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
CPRQRESET METHODMANUAL
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.938
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 20.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 208.0
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 125.0 AND DC 50.0
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6
CMLPTHREAD QUANTITY PER INCH32
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
AKPXPOLE QUANTITY3
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES NOMINAL 0.140
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.611
APNQARC QUENCHING METHODAIR

Supersedes

This item replaces cancelled NIIN 001358529. An older drawing citing one of those numbers resolves here.