Home / MS parts / NSN 5925-00-856-8103
NSN 5925-00-856-8103  ·  NIIN 008568103  ·  FSC 5925
NO DASHES 5925008568103
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

36 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 26.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 208.0
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 14.000
FREQFREQUENCY IN HERTZ400.0
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 2.500
ADATBODY WIDTHINCHES NOMINAL 2.250
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.938
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.750
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.062
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 0.750
AJECBOSS HEIGHTINCHES NOMINAL 0.140
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.471
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDMOISTURE RESISTANT AND FUNGUS RESISTANT
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CMLPTHREAD QUANTITY PER INCH32
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 150 PCT 7.000 AND MAXIMUM AT 150 PCT 500.000
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CQJXNOMINAL THREAD SIZEINCHES 0.138
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6
CPRWACTUATOR FUNCTIONTRIP-RESET