Home / MS parts / NSN 5925-00-949-7359
NSN 5925-00-949-7359  ·  NIIN 009497359  ·  FSC 5925
NO DASHES 5925009497359
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

37 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 14.000
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 0.750
ADATBODY WIDTHINCHES NOMINAL 2.250
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
ADAQBODY LENGTHINCHES NOMINAL 2.500
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.062
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
AJECBOSS HEIGHTINCHES NOMINAL 0.140
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 5.0
AKPXPOLE QUANTITY3
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 9.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDEXPLOSION RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
FREQFREQUENCY IN HERTZ400.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6
CMLPTHREAD QUANTITY PER INCH32
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.471
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.938
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.750
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS MINIMUM 7.000 AND MAXIMUM 50.000
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1000.0
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
AAQLBODY STYLE

Supersedes

This item replaces cancelled NIINs 009412146 · 009851505. An older drawing citing one of those numbers resolves here.