NSN 5925-00-096-5165 · NIIN 000965165 · FSC 5925
NO DASHES 5925000965165
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
39 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 2.510 |
| ADAT | BODY WIDTH | INCHES MINIMUM 1.437 AND INCHES MAXIMUM 1.563 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MINIMUM 1.660 AND INCHES MAXIMUM 1.960 |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES MINIMUM 0.719 AND INCHES MAXIMUM 0.781 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES MINIMUM 2.046 AND INCHES MAXIMUM 2.078 |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES MINIMUM 0.719 AND INCHES MAXIMUM 0.781 |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| ZZZK | SPECIFICATION/STANDARD DATA | GOVERNMENT SPECIFICATION 81349--IL-C-55629 TO 3 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 2.553 |
| AKPX | POLE QUANTITY | 2 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 4 |
| AJEC | BOSS HEIGHT | INCHES MINIMUM 0.109 AND INCHES MAXIMUM 0.171 |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 10.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 240.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 1000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.138 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 0.130 AND MAXIMUM AT 200 PCT 1.600 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| MATT | MATERIAL | CASE PLASTIC |
| TEST | TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-55629 |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | THREADED STUD 4 |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 2 |
| CPRQ | RESET METHOD | MANUAL |
Supersedes
This item replaces cancelled NIINs 003242902 · 007754093 · 008400651 · 008891045 · 009568329. An older drawing citing one of those numbers resolves here.