Home / MS parts / NSN 5925-01-216-6109
NSN 5925-01-216-6109  ·  NIIN 012166109  ·  FSC 5925
NO DASHES 5925012166109
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

46 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAJETHREAD PITCH DIAMETERSINCHES 0.3503 TO 0.3537
AAQLBODY STYLE
ABXDBUSHING LENGTHINCHES MAXIMUM 0.380
ADAQBODY LENGTHINCHES MAXIMUM 1.500
ADATBODY WIDTHINCHES MAXIMUM 1.875
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 0.844 AND INCHES MAXIMUM 0.906
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.594 AND INCHES MAXIMUM 0.656
AEFPNONTURN DEVICE RADIUSINCHES NOMINAL 0.875
AEFQNONTURN DEVICE LENGTHINCHES NOMINAL 0.199
AEFSNONTURN DEVICE DIAMETERINCHES NOMINAL 0.250
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.780
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING WITH PANEL SEAL 1
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEFIRST LOCATION AMPERES DC 15.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLETHIRD LOCATION AMPERES AC 5.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESECOND LOCATION AMPERES AC 2.5
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSECOND LOCATION AC 240.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSTHIRD LOCATION AC 240.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSFIRST LOCATION DC 50.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSECOND LOCATION AC 300.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSFIRST LOCATION DC 500.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSTHIRD LOCATION AC 300.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.375
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSECOND LOCATION MINIMUM AT 200 PCT 0.200 AND MAXIMUM AT 200 PCT 1.700
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTFIRST LOCATION MAXIMUM AT 200 PCT 0.050
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTTHIRD LOCATION MINIMUM AT 200 PCT 0.200 AND MAXIMUM AT 200 PCT 1.700
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND SHOCKPROOF AND VIBRATIONPROOF
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 5.400
FREQFREQUENCY IN HERTZ60.0
THSDTHREAD SERIES DESIGNATORUNEF
TTQYTERMINAL TYPE AND QUANTITYWIRE HOOK 6