Home / MS parts / NSN 5925-00-761-4505
NSN 5925-00-761-4505  ·  NIIN 007614505  ·  FSC 5925
NO DASHES 5925007614505
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

29 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
ABXDBUSHING LENGTHINCHES MAXIMUM 0.380
ADAQBODY LENGTHINCHES MAXIMUM 1.500
THSDTHREAD SERIES DESIGNATORUNEF
TTQYTERMINAL TYPE AND QUANTITYWIRE HOOK 2
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 10.0
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.375
AAQLBODY STYLE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 0.060 AND MAXIMUM AT 200 PCT 0.090
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED
FREQFREQUENCY IN HERTZ60.0
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 300.0
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.605
AKPXPOLE QUANTITY1
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING 1
ADATBODY WIDTHINCHES MAXIMUM 0.625
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 0.875