Home / MS parts / NSN 5925-00-409-3617
NSN 5925-00-409-3617  ·  NIIN 004093617  ·  FSC 5925
NO DASHES 5925004093617
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

36 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.940
AAJETHREAD PITCH DIAMETERSINCHES 0.1177 TO 0.1214
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 2.480 AND INCHES MAXIMUM 2.500
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 5.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 250.0
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.050 AND INCHES MAXIMUM 2.070
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
ADATBODY WIDTHINCHES MAXIMUM 0.750
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.475
AKPXPOLE QUANTITY1
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 22.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 3.700
FREQFREQUENCY IN HERTZ50.0 OR 60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 2
CMLPTHREAD QUANTITY PER INCH32
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 5000.0
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES NOMINAL 0.150
CPRQRESET METHODMANUAL