Circuit Breakers

Technical characteristics

45 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 2.480 AND INCHES MAXIMUM 2.520
ADATBODY WIDTHINCHES MINIMUM 1.510 AND INCHES MAXIMUM 1.530
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.660 AND INCHES MAXIMUM 1.960
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.052 AND INCHES MAXIMUM 2.072
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.130 AND INCHES MAXIMUM 0.150
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 2.392
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 4
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEFIRST LOCATION AMPERES DC 35.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSFIRST LOCATION DC 65.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSECOND LOCATION DC 35.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS DC 1000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICSECOND LOCATION INSTANTANEOUS
CPRLTRIP RELEASE CHARACTERISTICFIRST LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 2
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 2
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP W/AUXILIARY LOAD TERMINAL
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQSMSWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT EACH POLE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTFIRST LOCATION MINIMUM AT 200 PCT 0.600 AND MAXIMUM AT 200 PCT 8.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
CRTKSWITCH TERMINAL TYPEQUICK DISCONNECT, MALE
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 10.0 AND DC 4.0
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 250.0 AND DC 30.0
CTJSUNPACKAGED UNIT WEIGHTPOUNDS NOMINAL 6.438
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 4