| MRC | Requirement | Value |
|---|---|---|
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 2 |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CPRQ | RESET METHOD | MANUAL |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES MINIMUM 0.719 AND INCHES MAXIMUM 0.781 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES MINIMUM 2.046 AND INCHES MAXIMUM 2.078 |
| AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES MINIMUM 0.719 AND INCHES MAXIMUM 0.781 |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | INCHES MINIMUM 0.109 AND INCHES MAXIMUM 0.171 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 2.800 |
| AKPX | POLE QUANTITY | 2 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | AC 10.0 AND DC 2.0 |
| CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | AC 250.0 AND DC 50.0 |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| MATT | MATERIAL | CASE PLASTIC |
| TEST | TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-55629 |
| CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | ALARM 1 |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| ADAT | BODY WIDTH | INCHES MINIMUM 1.437 AND INCHES MAXIMUM 1.563 |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.138 |
| CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 0.130 AND MAXIMUM AT 200 PCT 1.600 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT |
| CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MINIMUM 1.660 AND INCHES MAXIMUM 1.960 |
| AAJE | THREAD PITCH DIAMETERS | INCHES 0.1177 TO 0.1214 |
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 2.510 |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | THREADED STUD 4 |
| ZZZK | SPECIFICATION/STANDARD DATA | GOVERNMENT SPECIFICATION 81349--IL-C-55629 TO 4 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 240.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 1000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 30.0 |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 4 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |