| MRC | Requirement | Value |
|---|---|---|
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES NOMINAL 22.000 |
| ADAT | BODY WIDTH | INCHES NOMINAL 16.000 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 13.625 |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | INCHES NOMINAL 0.406 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 19.750 |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 4.000 |
| AJEC | BOSS HEIGHT | INCHES NOMINAL 0.875 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES NOMINAL 12.781 |
| AKPX | POLE QUANTITY | 3 |
| APNQ | ARC QUENCHING METHOD | AIR |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | UNTHREADED HOLE(S) 8 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 1600.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 500.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 75000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS THERMAL-MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS INSTANTANEOUS AND TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 600 PCT 20.000 AND MAXIMUM AT 600 PCT 32.000 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | ALL LOCATIONS CELSIUS NOMINAL 50.0 |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| MATT | MATERIAL | CASE PLASTIC |
| TTQY | TERMINAL TYPE AND QUANTITY | BUS BAR 6 |
| ZZZT | NONDEFINITIVE SPEC/STD DATA | TYPE AQB-A1601 |