Home / MS parts / NSN 5925-00-931-1812
NSN 5925-00-931-1812  ·  NIIN 009311812  ·  FSC 5925
NO DASHES 5925009311812
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

34 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.052 AND INCHES MAXIMUM 2.072
AAQLBODY STYLE
AJECBOSS HEIGHTINCHES MINIMUM 0.130 AND INCHES MAXIMUM 0.150
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
AFJNFRAGILITY FACTORMODERATELY RUGGED
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 2.461 AND INCHES MAXIMUM 2.481
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 250.0
CMLPTHREAD QUANTITY PER INCH32
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 2
ADATBODY WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.928 AND INCHES MAXIMUM 1.948
AKPXPOLE QUANTITY1
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 4.000 AND MAXIMUM AT 200 PCT 10.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 4.250
FREQFREQUENCY IN HERTZ60.0
ADAQBODY LENGTHINCHES MINIMUM 2.490 AND INCHES MAXIMUM 2.510
CQJXNOMINAL THREAD SIZEINCHES 0.138
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 1000.0
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 2.0
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE