Home / MS parts / NSN 5925-01-270-5250
NSN 5925-01-270-5250  ·  NIIN 012705250  ·  FSC 5925
NO DASHES 5925012705250
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

40 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 6.500
ADATBODY WIDTHINCHES NOMINAL 4.125
ADAUBODY HEIGHTINCHES NOMINAL 5.125
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 5.562
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.375
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.281
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.625
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 2.750
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES NOMINAL 0.188
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODAIR
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 4
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 50.0 AND AMPERES DC 50.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 500.0 AND DC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 15000.0 AND DC 10000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS RELAY TRIP
CQSMSWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS NOMINAL AT 200 PCT 150.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
CRTKSWITCH TERMINAL TYPESCREW
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 50.0 AND DC 50.0
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 500.0 AND DC 250.0
FREQFREQUENCY IN HERTZ60.0 OR 400.0
MATTMATERIALCASE PLASTIC
TTQYTERMINAL TYPE AND QUANTITYSCREW 6