Home / MS parts / NSN 5925-00-938-3446
NSN 5925-00-938-3446  ·  NIIN 009383446  ·  FSC 5925
NO DASHES 5925009383446
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

29 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
ADAUBODY HEIGHTINCHES NOMINAL 4.344
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
CBBLFEATURES PROVIDEDADJUSTABLE TRIP RELEASE
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.375
CPRWACTUATOR FUNCTIONTRIP-RESET
AJECBOSS HEIGHTINCHES NOMINAL 0.188
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 15000.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 100.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 500.0
ADAQBODY LENGTHINCHES NOMINAL 6.500
ADATBODY WIDTHINCHES NOMINAL 4.125
AKPXPOLE QUANTITY3
AXHRMOUNTING FACILITY TYPE AND QUANTITYCLIP 6
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
FREQFREQUENCY IN HERTZ60.0 OR 400.0
MATTMATERIALCASE PLASTIC
TTQYTERMINAL TYPE AND QUANTITYCOMPRESSION 6
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
AAQLBODY STYLE
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0
CPRQRESET METHODMANUAL
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
CPSFADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPSALL LOCATIONS AC 500.0 TO 1400.0

Supersedes

This item replaces cancelled NIIN 011118309. An older drawing citing one of those numbers resolves here.