NSN 6120-01-679-7856 · NIIN 016797856 · FSC 6120
NO DASHES 6120016797856
In Stock
TRANSFORMER,POWER
Transformers: Distribution and Power Station
Technical characteristics
8 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| ADAT | BODY WIDTH | INCHES NOMINAL 37.89 |
| SPCL | SPECIAL TEST FEATURES | COMPLIANT WITH THE SEISMIC REQUIREMENTS OF ASCE/SEI 7 |
| ZZZT | NONDEFINITIVE SPEC/STD DATA | WEIGHT 4.03LB |
| ADAU | BODY HEIGHT | INCHES NOMINAL 71.00 |
| CWJS | WINDING OPERATING VOLTAGE | FIRST COMPONENT ALL PRIMARY AC VOLTS NOMINAL 480.0 |
| FEAT | SPECIAL FEATURES | DISTRIBUTION TRANSFORMER RATING: 300 KVA HERTZ: 60 PHASE: 3 PHASE INPUT VOLTAGE: 480 V DELTA OUTPUT VOLTAGE: 208Y/120 V CURRENT DISTORTION K FACTOR: K-3 COIL MATERIAL: COPPER TEMPERATURES RISE: 80 DEGREES C INSULATION RATING: 220 DEGREES C INSULATED IMPULSE VOLTAGE RATED: 10KV TYPE OF COLLING: NATURAL CONVECTION MOUNTING SUPPORT: FLOOR |
| ADAQ | BODY LENGTH | INCHES NOMINAL 48.26 |
| ACZB | FREQUENCY RATING | FIRST COMPONENT HERTZ NOMINAL 60.0 |