NSN 5925-01-271-1646 · NIIN 012711646 · FSC 5925
NO DASHES 5925012711646
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
25 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES NOMINAL 6.000 |
| ADAT | BODY WIDTH | INCHES NOMINAL 4.125 |
| ADAU | BODY HEIGHT | INCHES NOMINAL 3.375 |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 1.375 |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | INCHES NOMINAL 0.438 |
| AJEC | BOSS HEIGHT | INCHES NOMINAL 0.125 |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | UNTHREADED HOLE(S) 4 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 100.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 600.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 14000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS THERMAL-MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS INSTANTANEOUS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | ALL LOCATIONS CELSIUS NOMINAL 40.0 |
| FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 |
| MATT | MATERIAL | CASE PLASTIC |
| TTQY | TERMINAL TYPE AND QUANTITY | COMPRESSION 6 |
Supersedes
This item replaces cancelled NIIN 008980193. An older drawing citing one of those numbers resolves here.