NSN 5925-00-889-0768 · NIIN 008890768 · FSC 5925
NO DASHES 5925008890768
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
21 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 12.5 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 230.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 2000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND MOISTURE RESISTANT |
| AKPX | POLE QUANTITY | 2 |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.138 |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 |
| CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | ALL LOCATIONS NOMINAL 3600.000 |
| CPRQ | RESET METHOD | MANUAL |
| MATT | MATERIAL | CASE PLASTIC |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | TAB, SOLDER LUG 4 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 4 |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 3.000 AND MAXIMUM AT 200 PCT 10.000 |
Supersedes
This item replaces cancelled NIIN 002795390. An older drawing citing one of those numbers resolves here.