Technical characteristics

27 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 3.000
ADATBODY WIDTHINCHES NOMINAL 2.000
ADAUBODY HEIGHTINCHES NOMINAL 2.375
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.000
AJECBOSS HEIGHTINCHES NOMINAL 0.187
AKPXPOLE QUANTITY2
AXHRMOUNTING FACILITY TYPE AND QUANTITYCLIP 2
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 20.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 10000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT140.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 9.000 AND MAXIMUM AT 200 PCT 60.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
TTQYTERMINAL TYPE AND QUANTITYCLIP 2 AND COMPRESSION 2