NSN 5925-00-842-7299 · NIIN 008427299 · FSC 5925
NO DASHES 5925008427299
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
32 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AAQL | BODY STYLE | |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| ADAT | BODY WIDTH | INCHES MAXIMUM 0.750 |
| ABXD | BUSHING LENGTH | INCHES NOMINAL 0.250 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING 1 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 1.375 |
| TTQY | TERMINAL TYPE AND QUANTITY | SCREW 2 |
| ZZZK | SPECIFICATION/STANDARD DATA | GOVERNMENT STANDARD 96906--S24509 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 0.906 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES NOMINAL 1.312 |
| FREQ | FREQUENCY IN HERTZ | 400.0 |
| TEST | TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-5809 |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.469 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 200 PCT 10.000 AND MAXIMUM AT 200 PCT 60.000 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION RESISTANT AND MOISTURE RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | SINGLE LOCATION CELSIUS NOMINAL 25.0 |
| AKPX | POLE QUANTITY | 1 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES AC 35.0 AND AMPERES DC 35.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION AC 115.0 AND DC 28.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SINGLE LOCATION AC 3500.0 AND DC 6000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | SINGLE LOCATION THERMAL |
| CPRL | TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SINGLE LOCATION SERIES TRIP |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPRQ | RESET METHOD | MANUAL |
| THSD | THREAD SERIES DESIGNATOR | UNS |
Supersedes
This item replaces cancelled NIIN 008184812. An older drawing citing one of those numbers resolves here.