NSN 5925-00-752-6433 · NIIN 007526433 · FSC 5925
NO DASHES 5925007526433
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
32 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| CPRH | CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.138 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| AKPX | POLE QUANTITY | 1 |
| ADAT | BODY WIDTH | INCHES NOMINAL 0.750 |
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES NOMINAL 2.189 |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 |
| CPRQ | RESET METHOD | MANUAL |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 2 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SINGLE LOCATION AC 2000.0 AND DC 3000.0 |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SINGLE LOCATION SERIES TRIP |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 1.188 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES AC 35.0 AND AMPERES DC 35.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION AC 115.0 AND DC 28.0 |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 1.812 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 200 PCT 15.000 AND MAXIMUM AT 200 PCT 55.000 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | SINGLE LOCATION CELSIUS NOMINAL 25.0 |
| FREQ | FREQUENCY IN HERTZ | 400.0 |
| TEST | TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-5809 |
| TTQY | TERMINAL TYPE AND QUANTITY | TAB W/SCREW 2 |
| ZZZK | SPECIFICATION/STANDARD DATA | GOVERNMENT STANDARD 96906--S25337 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES NOMINAL 2.000 |
| CPRJ | TRIP RELEASE METHOD | SINGLE LOCATION THERMAL |
| CPRL | TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION TIME DELAY |
Supersedes
This item replaces cancelled NIINs 002419771 · 005054092 · 005782661. An older drawing citing one of those numbers resolves here.