NSN 5925-01-296-4365 · NIIN 012964365 · FSC 5925
NO DASHES 5925012964365
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
23 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AAQL | BODY STYLE | |
| ABXD | BUSHING LENGTH | INCHES NOMINAL 0.250 |
| ADAQ | BODY LENGTH | INCHES NOMINAL 0.780 |
| ADAT | BODY WIDTH | INCHES NOMINAL 0.593 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 0.593 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES NOMINAL 1.525 |
| AKPX | POLE QUANTITY | 4 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | TERMINAL 2 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES DC 20.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 115.0 AND DC 28.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 2000.0 AND DC 2000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERVOLTAGE |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS THERMAL |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 130.0 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS NOMINAL AT 130 PCT 3600.000 |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | ALL LOCATIONS FAHRENHEIT MAXIMUM 71.0 |
| FREQ | FREQUENCY IN HERTZ | 380.0 OR 420.0 |
| TTQY | TERMINAL TYPE AND QUANTITY | SCREW 2 |
| ZZZK | SPECIFICATION/STANDARD DATA | GOVERNMENT STANDARD 96906--S26574 |