26 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CRCFTRIP RELEASE AMBIENT TEMP RATINGSINGLE LOCATION CELSIUS NOMINAL 40.0
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
MATTMATERIALCASE PLASTIC
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 2
AJECBOSS HEIGHTINCHES NOMINAL 0.250
AKPXPOLE QUANTITY1
AXHRMOUNTING FACILITY TYPE AND QUANTITYTERMINAL 2
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
FREQFREQUENCY IN HERTZ60.0
ADATBODY WIDTHINCHES NOMINAL 1.000
ADAUBODY HEIGHTINCHES NOMINAL 2.312
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 60.000 AND MAXIMUM AT 200 PCT 300.000
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 3.344
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODSINGLE LOCATION THERMAL-MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 10000.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 240.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 20.0