Home / MS parts / NSN 5925-00-500-6809
NSN 5925-00-500-6809  ·  NIIN 005006809  ·  FSC 5925
NO DASHES 5925005006809
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

17 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.281
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 225.0 AND AMPERES DC 225.0
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 8
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 15000.0 AND DC 15000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
AKPXPOLE QUANTITY3
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
MATTMATERIALCASE PLASTIC
TTQYTERMINAL TYPE AND QUANTITYSCREW 6
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 600.0 AND DC 250.0
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 160.000 AND MAXIMUM AT 200 PCT 240.000

Supersedes

This item replaces cancelled NIIN 005619001. An older drawing citing one of those numbers resolves here.