NSN 5925-00-136-6935  ·  NIIN 001366935  ·  FSC 5925
NO DASHES 5925001366935
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

47 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ABXDBUSHING LENGTHINCHES NOMINAL 0.375
ADAQBODY LENGTHINCHES NOMINAL 1.495
ADATBODY WIDTHINCHES NOMINAL 1.872
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 0.875
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.625
AEFPNONTURN DEVICE RADIUSINCHES MINIMUM 0.620 AND INCHES MAXIMUM 0.630
AEFSNONTURN DEVICE DIAMETERINCHES NOMINAL 0.138
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 1.678
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND HERMETICALLY SEALED AND MOISTURE RESISTANT
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 4.500
FREQFREQUENCY IN HERTZ60.0
PMLCPRECIOUS MATERIAL AND LOCATIONSILVER CONTACT SURFACES
PRMTPRECIOUS MATERIALSILVER
THSDTHREAD SERIES DESIGNATORUNEF
TTQYTERMINAL TYPE AND QUANTITYWIRE HOOK 6
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESECOND LOCATION AMPERES AC 15.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLETHIRD LOCATION AMPERES AC 15.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSFIRST LOCATION AC 250.0 AND DC 10.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSECOND LOCATION AC 250.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSTHIRD LOCATION AC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSFIRST LOCATION AC 300.0 AND DC 500.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSECOND LOCATION AC 300.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSTHIRD LOCATION AC 300.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICFIRST LOCATION INSTANTANEOUS
CPRLTRIP RELEASE CHARACTERISTICSECOND LOCATION TIME DELAY
CPRLTRIP RELEASE CHARACTERISTICTHIRD LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.375
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSECOND LOCATION MINIMUM AT 200 PCT 1.000 AND MAXIMUM AT 200 PCT 4.000
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTTHIRD LOCATION MINIMUM AT 200 PCT 1.000 AND MAXIMUM AT 200 PCT 4.000
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEFIRST LOCATION AMPERES AC 15.0 AND MILLIAMPERES DC 50.0
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING WITH PANEL SEAL 1