34 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYQUICK DISCONNECT, MALE 2
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 1.985 AND INCHES MAXIMUM 2.015
ADATBODY WIDTHINCHES MINIMUM 0.745 AND INCHES MAXIMUM 0.755
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.555 AND INCHES MAXIMUM 1.565
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 1000.0
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 1.655 AND INCHES MAXIMUM 1.665
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.125 AND INCHES MAXIMUM 0.135
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 1.875 AND INCHES MAXIMUM 1.885
AKPXPOLE QUANTITY1
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 2.500
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 2.0
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 20.000