NSN 5925-01-017-0136 · NIIN 010170136 · FSC 5925
NO DASHES 5925010170136
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
31 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AAQL | BODY STYLE | |
| ABTD | MOUNTING SLOT WIDTH | INCHES NOMINAL 0.250 |
| ADAQ | BODY LENGTH | INCHES NOMINAL 6.310 |
| ADAT | BODY WIDTH | INCHES NOMINAL 2.750 |
| ADAU | BODY HEIGHT | INCHES NOMINAL 3.380 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 5.250 |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 1.375 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 4.880 |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 2.500 |
| AJEC | BOSS HEIGHT | INCHES NOMINAL 0.187 |
| AKPX | POLE QUANTITY | 2 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | SLOT 4 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 10.0 AND AMPERES DC 10.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 600.0 AND DC 250.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 14000.0 AND DC 10000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS THERMAL-MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS INSTANTANEOUS AND TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 30.000 AND MAXIMUM AT 200 PCT 150.000 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | ALL LOCATIONS CELSIUS NOMINAL 40.0 |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| MATT | MATERIAL | CASE PLASTIC |
| TTQY | TERMINAL TYPE AND QUANTITY | COMPRESSION 4 |