Home / MS parts / NSN 5925-00-587-1341
NSN 5925-00-587-1341  ·  NIIN 005871341  ·  FSC 5925
NO DASHES 5925005871341
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

36 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS RELAY TRIP
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 14.000
FREQFREQUENCY IN HERTZ60.0
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 0.300 AND MAXIMUM AT 200 PCT 0.900
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND GENERAL PURPOSE AND VIBRATION RESISTANT
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.062
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.500
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.611
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 10.0
MATTMATERIALCASE PLASTIC
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.500
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS MINIMUM 1.500 AND MAXIMUM 6.000
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CQJXNOMINAL THREAD SIZEINCHES 0.138
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 2.500
ADATBODY WIDTHINCHES NOMINAL 2.250
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.938
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 115.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 2000.0
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 12
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC