NSN 5925-00-929-7273 · NIIN 009297273 · FSC 5925
NO DASHES 5925009297273
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
31 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 2 |
| AKPX | POLE QUANTITY | 1 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION AC 120.0 AND DC 30.0 |
| ADAT | BODY WIDTH | INCHES MAXIMUM 0.750 |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 2.500 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 1.812 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 2.000 |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SINGLE LOCATION SERIES TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.138 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 200 PCT 18.000 AND MAXIMUM AT 200 PCT 80.000 |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 |
| CPRQ | RESET METHOD | MANUAL |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION RESISTANT AND MOISTURE RESISTANT |
| FREQ | FREQUENCY IN HERTZ | 400.0 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 1.188 |
| TEST | TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-5809 |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | SCREW 2 |
| ZZZK | SPECIFICATION/STANDARD DATA | GOVERNMENT STANDARD 96906--S25304 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES AC 5.0 AND AMPERES DC 5.0 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| AAQL | BODY STYLE | |
| CPRL | TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION TIME DELAY |
| CPRJ | TRIP RELEASE METHOD | SINGLE LOCATION MAGNETIC |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SINGLE LOCATION AC 3500.0 AND DC 3000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
Cross-references
3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.
| Manufacturer part number | CAGE |
|---|---|
| MIL-C-5809 | 81349 |
| MS25304-5 | 96906 |
| 5925009297273 | SCY13 |